Thread Diameter (mm) 16
Hole Diameter (mm) 25
Maximum Fixture Thickness (mm) 10
Fixture Clearance Hole (mm) 18
Embedment Depth (mm) 110
Minimum Hole Depth (mm) 125
Structure Thickness (mm) 200
Installation Torque (Nm) 110
Installation Instructions
1. Drill correct diameter hole to correct depth.
2. Clean hole by brushing and blowing to remove all dust and drilling debris.
3. Insert assembled anchor through fixture into concrete.
4. Position fixture, Insert bolt, Tighten with torque wrench to recommended torque.
Non-Cracked concrete
Performance Data (20/25 Concrete)
Thread Diameter (mm) 16
Characteristic Resistance (kN) Tensile 48.9
Characteristic Resistance (kN) Shear 62.8
Design Resistance (kN) Tensile 27.1
Design Resistance (kN) Shear 50.2
Recommended (kN) Tensile 19.3
Recommended (kN) Shear 35.8
Design Spacing (mm) Tensile & Shear 285
Design Edge Distance (mm) Tensile 160
Design Edge Distance (mm) Shear 365